SplashLens / Jandy / Zodiac / JXi Gas Heater

Jandy / Zodiac E01: Ignition Failure

Jandy / Zodiac E01 reference for JXi Gas Heater: likely causes, next checks, and manual-verification reminders for pool service techs.

Jandy / Zodiac JXi Gas Heater HIGH Certified tech recommended

What It Means

Ignition Failure

Likely Causes

Next Checks

  1. Verify gas shutoff valve is open
  2. Check manifold gas pressure (3.5" WC natural, 10" LP)
  3. Inspect HSI — should glow bright orange, replace if cracked or dim
  4. Clean flame rod with fine emery cloth
  5. Check flue clearance from walls — minimum per install manual
  6. JXi auto-retries 3x then locks out; hold MODE to reset lockout

Verify Before Repair

SplashLens is a field reference, not a repair guarantee. Confirm the visible code, exact model, and current manufacturer procedure before replacing parts, bypassing safeties, or quoting a customer.