What It Means
No Flow Through Sample Cell
Likely Causes
- Sample line clogged
- Strainer dirty
- Flow switch failed
- Pump off or valves closed
Next Checks
- Open sample valves and clean strainer
- Flush sample line and flow cell
- Confirm controller flow switch closes with water movement
- Do not allow controller to feed chemical without verified flow interlock
Verify Before Repair